The Fire Safety Order 2005
The Regulatory Reform (Fire Safety) Order 2005 covers non-domestic premises and the shared parts of buildings with more than one home, including the common parts of an HMO. The responsible person must make a suitable and sufficient fire risk assessment and review it regularly. For a workplace that is usually the employer. Otherwise it is the person in control of the premises, or the owner.
The Fire Safety Act 2021
In a building with two or more sets of domestic premises, the Order also covers the structure, the external walls (including doors, windows and balconies) and the doors between flats and the common parts.
Fire Safety (England) Regulations 2022
In a building with two or more homes and shared escape routes, fire safety instructions must be displayed and given to residents, and residents must be told how to use fire doors. In buildings over 11 metres, the responsible person must check communal fire doors at least every three months. They must use best endeavours to check flat entrance doors at least every 12 months, and keep a record of the steps taken.
A full written record
Since 1 October 2023 every responsible person must make a written record of the assessment and of each review. The record must include the findings, the measures taken or planned and any group of people especially at risk. Before that, only employers with five or more staff, licensed premises and premises under an alterations notice had to keep a record, and only of the significant findings. Anyone appointed to help with the assessment must be competent, and in buildings with two or more homes the residents must be told who that is.